Can a power station run a well pump?

Running

1,000W

To start

6,555VA

Stations

9of 129

Franklin Electric's own figures for its 1/2 HP 2-wire submersible motor at 230 V: up to 1,000 W while it pumps (6 A at its maximum load) and 28.5 A for the instant it starts, about 6,555 volt-amps. A 230 V pump needs a 240 V outlet on the station: 10 of 129 stations have one of their own, and 9 of those also cover the start; the cheapest at its maker is the Jackery HomePower 3600 Pro Max ($2,099).

A well pump is wired into the house at 240 V through its pressure switch, so no station plugs straight into it: the station's 240 V outlet reaches it through a transfer switch or a power inlet that an electrician fits. Then two figures decide: the start, which lasts a moment but takes about 5 times the running current, and the energy, which depends on how many minutes a day the pump runs.

Your pump and your water use

Example: Franklin's 1/2 HP 2-wire motor, pumping 30 minutes a day. Choose your own over them.

9 of 10 stations with a 240 V outlet run and start it. The cheapest, the Jackery HomePower 3600 Pro Max, gives about 3 days of water at 30 minutes a day.

30 minutes a day is our example, not a measured household. To time your own, note the minutes from the click of the pressure switch that starts the pump to the click that stops it, and how many times it starts in a day; an outage, with no laundry or long showers, uses far less. The motor's size is on the pump's paperwork or its control box; a pump with a control box on the wall is 3-wire.

The 10 stations with a 240 V outlet of their own

Hours of pumping = rated Wh × 0.85 ÷ the motor's running watts, on a full station with no reserve; days = the full charge against your minutes of pumping a day and, where its maker states one, the station's own standby draw over the whole day (below). The start is checked against the station's surge figure at 240 V where its maker gives one apart, else its own; a station with no surge figure is held to its continuous rating.

Each station with a 240 V outlet and the pump above, most water first; "up to" marks the days of a station whose maker states no standby draw
Model240 V outletPumpingDays of waterMaker price
EcoFlow DELTA Pro Ultra X12,288 Wh an L14-30 (120/240 V, 30 A) and a 14-50 (120/240 V, 50 A) 10.4 h up to 20 daysstandby not stated $7,999
EcoFlow DELTA Pro Ultra6,144 Wh one 120/240 V 30 A outlet 5.2 h up to 10 daysstandby not stated $4,199
OUPES Guardian 6000 V24,608 Wh an L14-30R, a 14-50R and a 6-20R outlet 3.9 h up to 7.8 daysstandby not stated $2,699
EcoFlow DELTA Pro 34,096 Wh an L14-30R outlet (120/240 V) 3.4 h up to 6.9 daysstandby not stated $2,799
Anker SOLIX F38003,840 Wh an L14-30 and a 14-50 outlet (120/240 V) 3.2 h up to 6.5 daysstandby not stated $2,199.99
Pecron F5000LFP5,120 Wh an L14-30R outlet 4.3 h 3.9 dayswith its 30 W standby $2,199
Jackery HomePower 3600 Pro Max3,584 Wh a 14-50R outlet at 240 V 3.0 h 3 dayswith its 25 W standby $2,099
Jackery Explorer 5000 Plus5,040 Wh an L14-30R and a 14-50 outlet at 120/240 V, 30 A 4.2 h 2.8 dayswith its 50 W standby $3,499
Anker SOLIX F3800 Plus3,840 Wh an L14-30 and a 14-50 outlet (120/240 V) 3.2 h 2.4 dayswith its 40 W standby $2,399.99
BLUETTI Apex 3002,765 Wh a 14-50R outlet, with its voltage selector set to 240 V – Start falls short (3,840 W, no surge figure) $1,499

The other 119 stations list no 240 V outlet on the unit itself; a few reach 240 V by linking two units or through a separate hub, which their makers sell as a system (two Pecron pairs below). A plug adapter does not make 240 V from a 120 V outlet.

Two stations and a box: 240 V from a pair

Pecron joins two of its stations into one 120/240 V output through its 240V Connect Box, and sells the two and the box as one kit. The figure at 240 V is Pecron's own for the pair; it gives no surge figure at 240 V, so the start is held to that rating, as for a single station that gives none.

Two stations and the maker's 240 V box, with the pump above
PairAt 240 VPumpingDays of waterKit at the maker
2 × Pecron E3600LFP6,144 Wh together, with Pecron's 240V Connect Box 7,200 W"2*E3600LFP+ 240V series connection kit=7200W 240V output" 5.2 h up to 10 daysstandby not stated $2,097the same as the parts bought separately, sold out when readSee the kit at Pecron
2 × Pecron E3800LFP7,680 Wh together, with Pecron's 240V Connect Box 8,400 W"2*E3800LFP+ 240V box =8400W 240V output" 6.5 h 4.6 dayswith its 44 W standby $2,697the same as the parts bought separatelySee the kit at Pecron

Kit prices from one read of Pecron's US store, Oct 29, 2026: the kit, one station and the box, each on its own page. The kit's two carts cost nothing extra: Pecron's store sells each E3800LFP with a free cart.

One of each works too: Pecron's page for the box says it "is for 2*E3600LFP / 2*E3800LFP / 1*E3600LFP+1*E3800LFP", so one E3600LFP and one E3800LFP also make 240 V. Pecron gives no figure at 240 V for that pair, so it is not in the table.

What each motor draws, in Franklin's figures

From Franklin Electric's AIM manual (60 Hz submersible systems, 2026 edition, page 39: its 4-inch single-phase motors with the "G" suffix, at 230 V). The start is the locked rotor amps × 230 V; volt-amps are at least the real watts, so a station just short of a figure may still start the pump, and only a test with your own pump settles it.

Franklin 4-inch submersible motors at 230 V
MotorRunning, at mostLocked rotorTo startStations that run it
1/2 HP 2-wire 1,000 W 28.5 A 6,555 VA 9 of 129
3/4 HP 2-wire 1,350 W 36.9 A 8,487 VA 6 of 129
1 HP 2-wire 1,630 W 47.6 A 10,948 VA 2 of 129
1-1/2 HP 2-wire 2,170 W 62 A 14,260 VA 1 of 129
1/2 HP 3-wire 1,000 W 20.6 A 4,738 VA 9 of 129
3/4 HP 3-wire 1,350 W 29.7 A 6,831 VA 9 of 129
1 HP 3-wire 1,630 W 35.9 A 8,257 VA 6 of 129

Look for a control box on the wall near the pressure tank before you choose a station by these figures. A 3-wire pump has one, and its motor starts on less current: at 1 HP, 35.9 A against 47.6 A for the 2-wire motor, about 8,257 VA instead of 10,948, which 4 more stations cover. A 1/2 HP motor made for 115 V does not start any easier: Franklin gives it 58.8 A, about 6,762 VA at 115 V.

Connecting it

The pump's circuit runs from a two-pole breaker through the pressure switch, so the station feeds it only through transfer equipment: a transfer switch, or a power inlet with an interlock on the main panel, fitted by a licensed electrician, who also checks the station's outlet, the neutral and the grounding. Never feed a house through a wall outlet. The home-backup guide says what the electrician needs to know.

Before the outage: the setting that switches the outlet off

Between starts the pump draws nothing, so to the station its outlet looks idle, and the idle timers that save a battery would switch it off; the next time the pressure switch calls, nothing answers. What each maker says:

For the other 3 stations, the sources we read do not say; look for an AC timeout or energy-saving setting in the manual or app, and test it with the pump before you need it.

What changes these days

The pump draws its running watts only while it fills the pressure tank; between starts it draws nothing. The station does not rest: its inverter draws its own power all day while the 240 V outlet stays on for the pressure switch, so the days in the table count that standby draw where the maker states it. Their makers give the standby draw as up to 25 W for the Jackery HomePower 3600 Pro Max, about 30 W for the Pecron F5000LFP, about 40 W for the Anker SOLIX F3800 Plus and 50 W for the Jackery Explorer 5000 Plus, about 600, 720, 960 and 1,200 Wh a day, against about 590 Wh from the battery for 30 minutes of the 1/2 HP 2-wire motor: on those stations the standby takes more of the charge than the pumping. For the other 5, the manuals and maker pages we read give no standby figure, so their days leave it out and run long. Every start takes the locked-rotor current for a moment, so a station that covers the start once covers it every time, and the energy is set by the minutes, not the number of starts. A deeper well or a bigger pump runs longer for the same water. Rated watt-hours fall in the cold and with age. To size a whole outage with a fridge and other loads too, use the calculator with "120/240 V split-phase loads" as the connection.

Also: a sump pump, home backup, and every device.

Questions buyers ask

How many watts does a well pump use?

Franklin rates its 1/2 HP 2-wire submersible motor at 660 W at full load and up to 1,000 W at its maximum load, and its 1 HP motor at up to 1,630 W, all at 230 V. Starting takes far more: 28.5 A for the 1/2 HP, about 6,555 volt-amps for a moment.

Can a 3,000 W power station run a well pump?

Not a 1/2 HP 2-wire submersible on its own: it needs a 240 V outlet and about 6,555 W of surge for the start. 9 of the 129 stations we list have both. A 3-wire pump of the same size starts on about 4,738 VA, which 9 cover.

Your shortlist

Compare power stations

Runtime is rated capacity × 0.85 ÷ watts. Check startup draw and connections separately. Prices are the maker's, with the day they were checked.